Friday, October 5, 2007

Submersible Cables:

CABLE DESIGN: Submersible Pump cables is a specialized product to be used for submersible pumps in a deep well. The area of installation is physically restrictive, and the environment is very hostile. Relemac is designed and manufactured keeping in mind these factors to achieve the highest possible degree of reliability

650/1100 VOLTS RELEMAC 3CORE FLAT CABLES FOR SUBMERSIBLE PUMPS
CONDUCTOR PVC INSULATION PVC SHEATH CURRENT
Rating at
300C
Amps.
Approx
Weight
Kg./Km.
Nominal
Area in
Nos. & Dia.
of wire
Nominal
Thickness
Nominal
Core Dia.
Nominal
Thickness
Approx. Overall
Dimensions
Sq. mm. Nos. / mm mm mm mm Thickness
mm
Width
mm
1.5 22/0.30 0.8 3.25 1.15 6.0 12.8 16 125
2.5 36/0.30 0.9 3.84 1.15 6.4 14.6 20 175
4.0 56/0.30 1.0 4.65 1.15 7.4 17.2 28 235
6.0 85/0.30 1.0 5.30 1.15 7.9 18.7 34 325
10.0 140/0.30 1.0 6.60 1.40 9.9 23.7 46 525
16.0 226/0.30 1.0 8.20 1.40 11.4 28.0 62 785
25.0 354/0.30 1.2 10.10 2.00 14.7 35.5 79 1270
35.0 495/0.30 1.2 11.50 2.00 16.2 39.5 98 1640
50.0 703/0.30 1.4 13.60 2.20 18.3 45.5 125 2080
70.0 440/0.45 1.4 15.30 2.20 20.0 51.0 156 2830
95.0 475/0.50 1.6 18.00 2.40 23.5 60.0 180 3620
Note :
  • The number of wires is approximate and wire diameter is nominal; they shall be such as to satisfy the requirements of conductor resistance as per Class 5 of IEC 60228 / DIN VDE 0295 / IS 8130 / BS 6360
  • 4 core and 5 core flat cables are available on request.

RELEMAC DOUBLE SHEATHED ROUND CABLES FOR SUBMERSIBLE PUMPS
650 / 1100 VOLTS
Nos. of cores
and
core area
Approx.
outside
diameter
Nos. of cores
and
core area
Aprox.
outside
diameter
Nos. X mm2 mm Nos. X mm2 mm
3 X 1.5
10.0
4 X 1.5
10.8
3 X 2.5
11.0
4 X 2.5
12.2
3 X 4
13.0
4 X 4
14.1
3 X 6
14.6
4 X 6
16.0
3 X 10
18.0
4 X 10
20.8
3 X 16
21.2
4 X 16
23.4
3 X 25
26.0
4 X 25
28.8
3 X 35
28.3
4 X 35
31.5
3 X 50
33.5
4 X 50
37.3
3 X 70
37.8
4 X 70
42.2
3 X 95
43.5
4 X 95
48.8

http://www.relemaccables.com/Submersiblecables.html